Simplex Fire
The Simplex Fire integrated system provides fire alarm integration.
Definitions
BACnet — Communication protocol for Building Automation and Control networks.
Setup
See the Data Servers page for information on configuring driver communication.
Compatibility
The Simplex Fire integrated system is compatible with:
- Portal Module Model 4100-6069 and 4010-9915
- BACnet Protocol Revision: ANSI/ASHRAE standard 135
BACnet Object Types
Asset | Object |
---|---|
Detector | BACNET_APPLICATION_TAG_ENUMERATED |
Fire Panel | BACNET_APPLICATION_TAG_ENUMERATED |
Fire Zone | BACNET_APPLICATION_TAG_ENUMERATED |
Prerequisites
Software | Minimum Version |
---|---|
.NET Framework | 4.7.2 |
IPFusion — Simplex Fire | 1.5 |
When completing your setup, be sure to have the Simplex Fire documentation available for reference.
Ports
These ports must be open in your network firewall for the integration to work.
Purpose | Default Value | Configurable |
---|---|---|
Communication Settings | 47808 | Yes |
Dataserver | 9520 | Yes |
Debug Tools | 9566 | No |
Supported BACpac Modules
Model | Description | Required RS-232 Module |
---|---|---|
4100-6069 | Single slot (2") BACpac Ethernet Module for
these file alarm control panels:
|
|
4010-9915 | Single block (4x5) BACpac Ethernet Module for 4010ES Series fire alarm control panels. | 4010-9918 |
Communication Configuration
In the integrated system configuration panel, you will find the Communication Settings. The below information is required.
IP Address | The IP Address of the Simplex Fire BACnet gateway. |
Port | The Port number for the Simplex Fire BACnet gateway connection. |
Device ID | The ID of the Simplex Fire BACnet gateway. |
Assets
Detector
This asset represents an alarm detector in the Simplex Fire system.
Required Property Grid Fields
BACnet Object Id | The ID of the BACnet entity the alarm detector asset represents. |
Supported States
Normal | The asset is online and in its default state. |
Fault | An issue has been detected in a connected asset. |
Masked | The asset has been masked over its true state. |
Acknowledged | An asset alarm has been acknowledged. |
No Communication | Communication has been lost with the driver or asset. This status can
also occur if the communication configuration for the system or asset is
invalid. Note: This status is required in all status
tables.
|
Active | The asset is online and in an alarm state. |
See the Configure a Status Table page for more information on configuring status tables.
Supported Commands
Mask | Mask the asset's true state. |
Acknowledge | Acknowledge an asset alarm. |
Reset | Resets the asset to its true hardware state. |
Cancel | Deselects all selected assets. |
New Note | Adding the New Note Command to your Command Table subscribes this asset to Notes, allowing an operator to attach Notes to this asset in Runtime. |
Workflow Trigger | Allows users to trigger Workflows to create custom commands. |
See the Command Tables page for more information on configuring command tables.
Fire Zone
This asset represents a fire zone in the Simplex Fire system.
Required Property Grid Fields
BACnet Object Id | The ID of the BACnet entity the alarm detector asset represents. |
Supported States
Normal | The asset is online and in its default state. |
Fault | An issue has been detected in a connected asset. |
Acknowledged | An asset alarm has been acknowledged. |
No Communication | Communication has been lost with the driver or asset. This status can
also occur if the communication configuration for the system or asset is
invalid. Note: This status is required in all status
tables.
|
Alarm | The asset is online and in an alarm state. |
See the Configure a Status Table page for more information on configuring status tables.
Supported Commands
Mask | Mask the asset's true state. |
Acknowledge | Acknowledge an asset alarm. |
Reset | Resets the asset to its true hardware state. |
Cancel | Deselects all selected assets. |
New Note | Adding the New Note Command to your Command Table subscribes this asset to Notes, allowing an operator to attach Notes to this asset in Runtime. |
Workflow Trigger | Allows users to trigger Workflows to create custom commands. |
See the Command Tables page for more information on configuring command tables.
Fire Panel
This asset represents a fire panel in the Simplex Fire system.
Required Property Grid Fields
BACnet Object Id | The ID of the BACnet entity the alarm detector asset represents. |
Supported States
Normal | The asset is online and in its default state. |
Fault | An issue has been detected in a connected asset. |
Masked | The asset has been masked over its true state. |
Acknowledged | An asset alarm has been acknowledged. |
No Communication | Communication has been lost with the driver or asset. This status can
also occur if the communication configuration for the system or asset is
invalid. Note: This status is required in all status
tables.
|
See the Configure a Status Table page for more information on configuring status tables.
Supported Commands
Mask | Mask the asset's true state. |
Acknowledge | Acknowledge an asset alarm. |
Reset | Resets the asset to its true hardware state. |
Cancel | Deselects all selected assets. |
New Note | Adding the New Note Command to your Command Table subscribes this asset to Notes, allowing an operator to attach Notes to this asset in Runtime. |
Workflow Trigger | Allows users to trigger Workflows to create custom commands. |
See the Command Tables page for more information on configuring command tables.
System
This asset represents the connection state of the Simplex Fire system.
Supported States
Normal | The asset is online and in its default state. |
Fault | An issue has been detected in a connected asset. |
Masked | The asset has been masked over its true state. |
Acknowledged | An asset alarm has been acknowledged. |
No Communication | Communication has been lost with the driver or asset. This status can
also occur if the communication configuration for the system or asset is
invalid. Note: This status is required in all status
tables.
|
See the Configure a Status Table page for more information on configuring status tables.
Supported Commands
Mask | Mask the asset's true state. |
Acknowledge | Acknowledge an asset alarm. |
Reset | Resets the asset to its true hardware state. |
Cancel | Deselects all selected assets. |
New Note | Adding the New Note Command to your Command Table subscribes this asset to Notes, allowing an operator to attach Notes to this asset in Runtime. |
Workflow Trigger | Allows users to trigger Workflows to create custom commands. |
See the Command Tables page for more information on configuring command tables.
Troubleshooting
Unable to Connect to Assets
If you are having trouble connecting to the assets in your system, the BACnet objects may be configured with the incorrect type. Ensure your BACnet object is configured to use the correct object type.
Logs from the driver and Runtime can be viewed in the Debug Tools client. These messages contain information which can provide further context for issues during initialization, or while actively running. This can help diagnose problems.