ILC LightLEEDer

The ILC LightLEEDer integrated system provides individual control of lighting ballasts, drivers, and controls. The ILC LightLEEDer system is integrated into IPFusion by design. For further information about this integration, please contact support.

Note: BACnet integrated systems support cross subdomain communication via BBMD (BACnet Broadcast Management Device) without the need for additional configuration in Designer.

Setup

See the Data Servers page for information on configuring driver communication.

Compatibility

The ILC LightLEEDer integrated system is compatible with LightLEEDer programmable lighting control panels using the BACnet IP add-on module.

BACnet Object Types

Asset Object
Light BACNET_APPLICATION_TAG_ENUMERATED
Light Zone BACNET_APPLICATION_TAG_ENUMERATED

Prerequisites

Software Minimum Version
IPFusion — ILC LightLEEDer 1.0
.NET Framework 4.7.2

When completing your setup, be sure to have the ILC LightLEEDer documentation available for reference.

Ports

These ports must be open in your network firewall for the integration to work.

Purpose Default Value Configurable
Communication Settings 47808 Yes
Dataserver 9520 Yes
Debug Tools 9566 No

Communication Configuration

You will find the Communication Settings in the integrated system configuration panel. The following information is required:

IP Address The IP Address of the BACnet gateway.
Port The Port for the BACnet gateway connection.
Device ID The Device ID of the BACnet gateway.
Note: Red X indicates an invalid or out of range value given for field.

Assets

Light

This asset represents a single light device in the ILC LightLEEDer system.

Required Property Grid Fields

BACnet ID The ID of the BACnet entity the asset represents.

View all properties

Supported States

Acknowledged An asset alarm has been acknowledged.
Masked The asset has been masked over its true state.
No Communication Communication has been lost with the driver or asset. This status can also occur if the communication configuration for the system or asset is invalid.
Note: This status is required in all status tables.
On The light is turned on.
Off The light is turned off.

See the Configure a Status Table page for more information on configuring status tables.

Supported Commands

Acknowledge Acknowledge an asset alarm.
Cancel Deselects all selected assets.
Mask Mask the asset's true state.
On Turns the light on.
Off Turns the light off.
Reset Resets the asset to its true hardware state.

See the Command Tables page for more information on configuring command tables.

Light Zone

Light zones are represented as predefined groups of lights configured using the ILC LightLEEDer proprietary software.

Required Property Grid Fields

BACnet ID The ID of the BACnet entity the asset represents.

View all properties

Supported States

Acknowledged An asset alarm has been acknowledged.
Fault An issue has been detected in a connected asset.
Masked The asset has been masked over its true state.
No Communication Communication has been lost with the driver or asset. This status can also occur if the communication configuration for the system or asset is invalid.
Note: This status is required in all status tables.
On The lighting zone is turned on.
Off The lighting zone is turned off.

See the Configure a Status Table page for more information on configuring status tables.

Supported Commands

Acknowledge Acknowledge an asset alarm.
Cancel Deselects all selected assets.
Mask Mask the asset's true state.
On Turns on the light zone.
Off Turns off the light zone.
Reset Resets the asset to its true hardware state.

See the Command Tables page for more information on configuring command tables.

System

This asset represents the connection from Runtime to the ILC LightLEEDer system.

View all properties

Supported States

Normal The asset is online and in its default state.
Fault An issue has been detected in a connected asset.
Masked The asset has been masked over its true state.
Acknowledged An asset alarm has been acknowledged.
No Communication Communication has been lost with the driver or asset. This status can also occur if the communication configuration for the system or asset is invalid.
Note: This status is required in all status tables.

See the Configure a Status Table page for more information on configuring status tables.

Supported Commands

Mask Mask the asset's true state.
Acknowledge Acknowledge an asset alarm.
Reset Resets the asset to its true hardware state.
Cancel Deselects all selected assets.

See the Command Tables page for more information on configuring command tables.

Troubleshooting

Unable to Connect to Assets

If you are having trouble connecting to the assets in your system, the BACnet objects may be configured with the incorrect type. Ensure your BACnet object is configured to use the correct object type.

Logs from the driver and Runtime can be viewed in the Debug Tools client. These messages contain information which can provide further context for issues during initialization, or while actively running. This can help diagnose problems.