DSC PowerSeries
The DSC PowerSeries integrated system provides access control integration.
Setup
See the Data Servers page for information on configuring driver communication.
Compatibility
The DSC PowerSeries integrated system is compatible with the below panels and is tested using the TL280R panel.
- 3G2080
- 3G2080R
- TL280
- TL280R
- TL2803G
- TL2803GR
- PCL-422
Prerequisites
Software | Minimum Version |
---|---|
IPFusion — DSC PowerSeries | 1.0 |
.NET Framework | 4.7.2 |
When completing your setup, be sure to have the DSC PowerSeries documentation available for reference.
Ports
These ports must be open in your network firewall for the integration to work.
Purpose | Default Value | Configurable |
---|---|---|
Communication Settings | 3073 | Yes |
Dataserver | 9648 | Yes |
Debug Tools | 9649 | No |
Communication Configuration
In the integrated system configuration panel, you will find the Communication Settings. The below information is required.
Address | The address of the server hosting the DSC PowerSeries driver. |
Port | The Port number for the DSC PowerSeries control panel connection. |
Integration Identification Number | The defined Integration Identification Number for your DSC panel. |
Integration Access Code | The Integration Access Code configured when setting up your DSC panel. |
Master Code | The Master Code configured when setting up your DSC panel. |
Assets
System Asset
This asset represents the connection to the DSC panel.
Supported States
Normal | The asset is online and in its default state. |
Masked | The asset has been masked over its true state. |
Fault | An issue has been detected in a connected asset. |
Acknowledged | An asset alarm has been acknowledged. |
No Communication | Communication has been lost with the driver or asset. This status can
also occur if the communication configuration for the system or asset is
invalid. Note: This status is required in all status
tables.
|
See the Configure a Status Table page for more information on configuring status tables.
Supported Commands
Mask | Mask the asset's true state. |
Acknowledge | Acknowledge an asset alarm. |
Reset | Resets the asset to its true hardware state. |
Cancel | Deselects all selected assets. |
See the Command Tables page for more information on configuring command tables.
Partition Asset
This asset represents a partition in the DSC system.
Required Property Grid Fields
Partition ID | The identifier for the partition this asset represents. |
Supported States
Masked | The asset has been masked over its true state. |
Fault | An issue has been detected in a connected asset. |
Acknowledged | An asset alarm has been acknowledged. |
No Communication | Communication has been lost with the driver or asset. This status can
also occur if the communication configuration for the system or asset is
invalid. Note: This status is required in all status
tables.
|
Disarmed | The partition is disarmed. |
Stay Armed | The partition is armed in stay mode. |
Stay Armed With No Entry Delay | The partition is armed in stay mode without a delay given for people to enter/exit the area first. |
Away Armed | The partition is armed in away mode. |
Away Armed With No Entry Delay | The partition is armed in away mode without a delay given for people to enter/exit the area first. |
Night Mode Armed | The partition is armed in night mode. |
In Alarm | An alarm is active within the partition. |
Ready | The partition is ready to be armed. |
Not Ready | The partition is not ready to be armed. |
See the Configure a Status Table page for more information on configuring status tables.
Supported Commands
Reset | Resets the asset to its true hardware state. |
Mask | Mask the asset's true state. |
Cancel | Deselects all selected assets. |
Acknowledge | Acknowledge an asset alarm. |
Disarm | Disarms the partition. |
Arm Stay Mode | Arms the partition in stay mode. |
No-Entry Arming in Stay Mode | Arms the partition in stay mode without providing a delay. |
Arm Away Mode | Arms the partition in away mode. |
No-Entry Arming in Away Mode | Arms the partition in away mode without providing a delay. |
Arm Night Mode | Arms the partition in night mode. |
Activate Output | Activates a specified output ID. |
Deactivate Output | Deactivates a specified output ID. |
Toggle Output | Activates a deactivated output by ID, and vice versa. |
See the Command Tables page for more information on configuring command tables.
Zone Asset
This asset represents a zone in the DSC system.
Required Property Grid Fields
Zone ID | The identifier for the zone this asset represents. |
Supported States
Masked | The asset has been masked over its true state. |
Fault | An issue has been detected in a connected asset. |
Acknowledged | An asset alarm has been acknowledged. |
No Communication | Communication has been lost with the driver or asset. This status can
also occur if the communication configuration for the system or asset is
invalid. Note: This status is required in all status
tables.
|
Bypassed | The zone is currently bypassed. |
Not Bypassed | The zone is not bypassed. |
In Alarm | An alarm is active in the zone. |
No Alarm | There are no active alarms in the zone. |
Open | The zone input is currently in an open-circuit state. |
Closed | The zone input is currently in a closed closed-circuit state. |
See the Configure a Status Table page for more information on configuring status tables.
Supported Commands
Mask | Mask the asset's true state. |
Acknowledge | Acknowledge an asset alarm. |
Reset | Resets the asset to its true hardware state. |
Cancel | Deselects all selected assets. |
Bypass | Bypasses the zone. |
Unbypass | Removes the bypass from the zone. |
See the Command Tables page for more information on configuring command tables.