The Eaton Fifth Light integrated system provides individual control of lighting ballasts, drivers, and controls.
Setup
See the Data Servers page for information on configuring driver communication.
Compatibility
The Eaton Fifth Light integrated system is compatible:
- Product Model Number FLT-BACNET
- Application Software Version: LMS 4.12.4
- BACnet Protocol Revision: ANSI/ASHRAE standard 135-2204 BACnet revision 2
Prerequisites
Software | Minimum Version |
---|---|
IPFusion — Eaton Fifth Light | 1.0 |
.NET Framework | 4.7.2 |
When completing your setup, be sure to have the Eaton Fifth Light documentation available for reference.
Ports
These ports must be open in your network firewall for the integration to work.
Purpose | Default Value | Configurable |
---|---|---|
Communication Settings | 47808 | Yes |
Dataserver | 9520 | Yes |
Debug Tools | 9566 | No |
Communication Configuration
You will find the Communication Settings in the integrated system configuration panel. The following information is required:
IP Address | The IP Address of the Fifth Light BACnet gateway. |
Port | The Port for the Fifth Light BACnet gateway connection. |
Device ID | The Device ID of the Fifth Light BACnet gateway. |
Override Priority | The Priority level of the command for the BACnet priority
array. Values available:
|
Assets
Light
This asset represents a single light device in the Eaton Fifth Light system.
Required Property Grid Fields
BACnet ID | The ID of the BACnet entity the asset represents. |
Supported States
Fault | An issue has been detected in a connected asset. |
Acknowledged | An asset alarm has been acknowledged. |
No Communication | Communication has been lost with the driver or asset. This status can
also occur if the communication configuration for the system or asset is
invalid. Note: This status is required in all status
tables.
|
On | For a single light, its power is set to 100%. For a group of lights, at least one light in the group is above 0%. |
On and Override | The asset has been set to the On state from Runtime, and is overriding a light value set outside of Runtime. |
Off | A single light, or all lights in a group, are set to 0% power. |
Off and Override | The asset has been set to the Off state from the Runtime, and is overriding a light value set outside of Runtime. |
Custom Range | The current power level of the light falls within the
range specified in the status configuration.
|
Custom Range and Override | The current power level of the light falls within the
range specified in the status configuration, and is
overriding a light value set outside of Runtime.
|
See the Configure a Status Table page for more information on configuring status tables.
Supported Commands
Mask | Mask the asset's true state. |
Acknowledge | Acknowledge an asset alarm. |
Reset | Resets the asset to its true hardware state. |
Cancel | Deselects all selected assets. |
On | Sets the light to 100% power.
|
Off | Sets light to 0% power.
|
Percent Dim |
Sets light to a specific power level.
|
Cancel Override | Cancels the On, Off, or Percent Dim command last sent and sets the device to the previous power level. |
See the Command Tables page for more information on configuring command tables.
Lighting Zone
Light zones are represented as predefined groups of lights configured using the Eaton Fifth Light proprietary software.
Required Property Grid Fields
BACnet ID | The ID of the BACnet entity the asset represents. |
Supported States
Fault | An issue has been detected in a connected asset. |
Masked | The asset has been masked over its true state. |
Acknowledged | An asset alarm has been acknowledged. |
No Communication | Communication has been lost with the driver or asset. This status can
also occur if the communication configuration for the system or asset is
invalid. Note: This status is required in all status
tables.
|
On | For a single light, its power is set to 100%. For a group of lights, at least one light in the group is above 0%. |
On and Override | The asset has been set to the On state from the Runtime, and is overriding a light value set outside of Runtime. |
Off | A single light, or all lights in a group, are set to 0% power. |
Off and Override | The asset has been set to the Off state from the Runtime, and is overriding a light value set outside of Runtime. |
Custom Range |
The current power level of the light falls within the
range specified in the status configuration.
|
Custom Range and Override | The current power level of the light falls within the
range specified in the status configuration, and is
overriding a light value set outside of Runtime.
|
See the Configure a Status Table page for more information on configuring status tables.
Supported Commands
Mask | Mask the asset's true state. |
Acknowledge | Acknowledge an asset alarm. |
Reset | Resets the asset to its true hardware state. |
Cancel | Deselects all selected assets. |
On |
Sets the light zone to 100% power.
|
Off |
Sets light zone to 0% power.
|
Percent Dim |
Sets light zone to a specific power level.
|
See the Command Tables page for more information on configuring command tables.
System
This asset represents the connection from Runtime to the Eaton Fifth Light system.
Supported States
Normal | The asset is online and in its default state. |
Fault | An issue has been detected in a connected asset. |
Masked | The asset has been masked over its true state. |
Acknowledged | An asset alarm has been acknowledged. |
No Communication | Communication has been lost with the driver or asset. This status can
also occur if the communication configuration for the system or asset is
invalid. Note: This status is required in all status
tables.
|
See the Configure a Status Table page for more information on configuring status tables.
Supported Commands
Mask | Mask the asset's true state. |
Acknowledge | Acknowledge an asset alarm. |
Reset | Resets the asset to its true hardware state. |
Cancel | Deselects all selected assets. |
See the Command Tables page for more information on configuring command tables.
Workflow Integration
System Commands
System commands are commands executed through Workflows at the system level. For more information about Workflows, see the Workflows section.
Change Light Level
Sets light or lighting zone to a specific power level for a specified amount of time.
Asset ID | The unique identifier for the light to change. |
Light Level | The power level for the light. |
Duration | How long in minutes the light will be set to this level. |
Troubleshooting
Logs from the driver and Runtime can be viewed in the Debug Tools client. These messages contain information which can provide further context for issues during initialization, or while actively running. This can help diagnose problems.