Johnson Controls P2000

The Johnson Controls P2000 integrated system provides access control integration.

Definitions

Compatibility

The Johnson Controls P2000 integrated system is compatible with software version 3.12 service pack 2.

Prerequisites

Software Minimum Version
.NET Framework 4.7.2

When completing your setup, be sure to have the Johnson Controls P2000 documentation available for reference.

Communication Configuration

In the integrated system configuration panel, you will find the Communication Settings. The below information is required.

Server Address The IP Address or host name of the Johnson Controls P2000 server.
Real Time Data Port The Port number for the Johnson Controls P2000 server connection listing for events.
Username The Username of the user to login as. This is typically a user created specifically for the Runtime connection.
Password The Password of the user to login as.
Note: Red X indicates an invalid or out of range value given for field.

Assets

Door

This asset represents a door in the Johnson Controls system.

Required Property Grid Fields

Duress Input The identifier for the Input device to use for Duress.
Forced Open Input The identifier for the Input device detecting if the door has been forcibly opened.
Glass Break Input The identifier for the Input device detecting if Glass on this door has been broken.
P2000 Name The Name identifying this door in the P2000 system.
Partition Name The Name of the Partition this door belongs to.
Propped Open Input The identifier for the Input device detecting if this door has been Propped Open.
Tamper Input The identifier of the Input device used to detect if this door has been tampered with.

View all properties

Supported States

No Communication Communication has been lost with the driver or asset. This status can also occur if the communication configuration for the system or asset is invalid.
Note: This status is required in all status tables.
Normal The asset is online and in its default state.
Masked The asset has been masked over its true state.
Acknowledged An asset alarm has been acknowledged.
Fault An issue has been detected in a connected asset.
Up The reader for this door is in a normal state.
Down An issue has been detected for this door's reader.
Lockout The door can not be unlocked.
Unlocked The door is unlocked.
Disabled This asset can not be interacted with.
Override The door has been unlocked temporarily.
Forced Open The door has been forcibly opened.
Held Open The door was unlocked, and is being held open for an extended period of time.
Glass Break An associated sensor has detected a glass break.
Duress A staff duress has been reported.
Locked The door is locked.
Tamper The asset has been tampered with.

See the Configure a Status Table page for more information on configuring status tables.

Supported Commands

Acknowledge Acknowledge an asset alarm.
Cancel Deselects all selected assets.
Mask Mask the asset's true state.
Reset Resets the asset to its true hardware state.
Lock Locks the door.
Pass Temporarily unlocks the door.
Unlock Unlocks the door.
Disable Stops the door from being able to be interacted with.
Enable Allows the door to be interacted with.
Set Access Level Sets the access level required for this door.

See the Command Tables page for more information on configuring command tables.

Input

This asset represents an input point in the Johnson Controls system.

Required Property Grid Fields

P2000 Name The Name identifying this input device in the P2000 system.
Partition Name The Name of the Partition this input belongs to.

View all properties

Supported States

No Communication Communication has been lost with the driver or asset. This status can also occur if the communication configuration for the system or asset is invalid.
Note: This status is required in all status tables.
Normal The asset is online and in its default state.
Masked The asset has been masked over its true state.
Acknowledged An asset alarm has been acknowledged.
Fault An issue has been detected in a connected asset.
Disabled The input device can not be interacted with.
Set Turns on the input point.
Short A hardware fault has been detected in this asset.
Open When the associated door has been open for an extended period of time.
Suppressed An alarm is being suppressed.

See the Configure a Status Table page for more information on configuring status tables.

Supported Commands

Acknowledge Acknowledge an asset alarm.
Cancel Deselects all selected assets.
Mask Mask the asset's true state.
Reset Resets the asset to its true hardware state.

See the Command Tables page for more information on configuring command tables.

Output

This asset represents an output point in the Johnson Controls system.

Required Property Grid Fields

P2000 Name The Name identifying the output asset in the P2000 system.
Partition Name The Name of the Partition the output device belongs to.

View all properties

Supported States

No Communication Communication has been lost with the driver or asset. This status can also occur if the communication configuration for the system or asset is invalid.
Note: This status is required in all status tables.
Normal The asset is online and in its default state.
Masked The asset has been masked over its true state.
Acknowledged An asset alarm has been acknowledged.
Fault An issue has been detected in a connected asset.
On The asset is currently on.
Off The asset is currently off.

See the Configure a Status Table page for more information on configuring status tables.

Supported Commands

Acknowledge Acknowledge an asset alarm.
Cancel Deselects all selected assets.
Mask Mask the asset's true state.
Reset Resets the asset to its true hardware state.
Set On Turns the output device on.
Set Slow Flash Sets the output device to slowly flash.
Set Fast Flash Sets the output device to flash quickly.
Set Preset Uses a command preset in the Johnson Controls configuration.

See the Command Tables page for more information on configuring command tables.

Alarm

This asset represents an alarm in the Johnson Controls system.

Required Property Grid Fields

P2000 Name The Name identifying this alarm in the P2000 system.
Partition Name The Name of the Partition this alarm belongs to.

View all properties

Supported States

No Communication Communication has been lost with the driver or asset. This status can also occur if the communication configuration for the system or asset is invalid.
Note: This status is required in all status tables.
Normal The asset is online and in its default state.
Masked The asset has been masked over its true state.
Acknowledged An asset alarm has been acknowledged.
Fault An issue has been detected in a connected asset.
Off The asset is currently off.

See the Configure a Status Table page for more information on configuring status tables.

Supported Commands

Acknowledge Acknowledge an asset alarm.
Cancel Deselects all selected assets.
Mask Mask the asset's true state.
Reset Resets the asset to its true hardware state.
Respond Flag the alarm as being responded to.
Complete Flag the alarm as being completed.

See the Command Tables page for more information on configuring command tables.

System

This asset represents the connection to the Johnson Controls system.

View all properties

Supported States

No Communication Communication has been lost with the driver or asset. This status can also occur if the communication configuration for the system or asset is invalid.
Note: This status is required in all status tables.
Normal The asset is online and in its default state.
Masked The asset has been masked over its true state.
Acknowledged An asset alarm has been acknowledged.
Fault An issue has been detected in a connected asset.

See the Configure a Status Table page for more information on configuring status tables.

Supported Commands

Acknowledge Acknowledge an asset alarm.
Cancel Deselects all selected assets.
Mask Mask the asset's true state.
Reset Resets the asset to its true hardware state.

See the Command Tables page for more information on configuring command tables.

Workflow Integration

System Commands

System commands are commands executed through Workflows at the system level. For more information about Workflows, see the Workflows section.

Set Access Levels

The Set Access Levels command is used to Set the Access Levels to a set of specified doors.

Table 1. Parameters
Access Level The Access Level being set for the doors.
Door Assets The Assets corresponding with the Doors.

Door Lock

The Door Lock command is used to lock a specified door.

Table 2. Parameters
Name The Name of the door asset.
Partition Name The Name of the Partition the door is located in.

Door Pass

The Door Pass command is used to temporarily unlock a door for a specified amount of time. Once the timer has expired, the doors are locked.

Table 3. Parameters
Name The Name of the door asset.
Partition Name The Name of the Partition the door is located in.
Unlock Time The Time, in seconds, a door will be Unlocked for.

Door Unlock

The Door Unlock command is used to Unlock a specified Door.

Table 4. Parameters
Name The Name of the door asset.
Partition Name The Name of the Partition the door is located in.

Troubleshooting

Logs from the driver and Runtime can be viewed in the Debug Tools client. These messages contain information which can provide further context for issues during initialization, or while actively running. This can help diagnose problems.